EARTH FAULT PROTECTION RELAY
Products Feature | |
Microprocessor based numerical relay | Definite time for low-set & high-set |
Current measurement based on fundamental frequency | Non-volatile fault value recording |
Low-set earth-fault | Programmable relay outputs |
High-set earth-fault | Five selectable IDMT charecteristic curves |
Local display of measured and set values | Complies with IEC 60255-26 standard |
SPECIFICATIONS | NX 232A-240VAC |
RATINGS | |
Current Rating (In) | 5A |
Frequency | 50 or 60 Hz |
Burden | < 0.3 VA at I |
Thermal Withstand | 4 x | Continuous |
SETTING RANGES | |
Low-set (I>) | : 0.1 A to 5.0 A, step 0.05 A / 2% to 100%, step 1% |
Low-set time set muttiplier (kt>) | : 0.05 to 1.0, step 0.01 |
Low-set definite time (t | : 0.05 to 99 sec , step 0.01 (0.05 to 1.0) / 0.1 (1.1 to 99) |
High-set (I>>) | : 0.1 A to 50 A or disable , step 0.1 A / 2% to 1000%, step 2% |
High set delay time (t>>) | : 0.05 sec to 2.5 sec , step 0.01 |
ACCURACY | |
Protection Thresholds | +5% |
Time Delay | 5% with a minimum of 50 ms |
AUXILIARY SUPPLY | |
Supply Voltage | 198 – 265 VAC |
VA Rating | 3 VA typical |
CONTACT SPECIFICATION | |
Contact Arrangement | Change-Over |
Contact Rating | 6A, 250 VAC (Cos p = 1) for Tripping Contact 5A, 250 VAC (Cos p = 1) for Signaling Contact |
Contact Material | Silver Alloy |
Operating Time | 15 ms max |
Expected Electrical Life | 100,000 operations at rated current |
Expected Mechanical Life | 5 x 10operations |
Approval | UL / CSA/VDE / TUV / SEMKO |
INDICATORS and DIMENSION | |
Auxiliary Supply | LED Indicator |
Pick-Up | LED Indicator |
Trip | 7-Segment Display and LED Indicator |
Dimension | 96 x 96 mm. |