SIMATIC S7-1500 Advanced Controllers
I/O modules
SIPLUS communication

-Modules for serial communication connections, scaled according to interface types, protocols, and performance
-4 versions with different physical transmission characteristics:
– RS 232C, max. 19.2 kbps
– RS 232C, max. 115.2 kbps
– RS 422/RS 485, max. 19.2 kbps
– RS 422/RS 485, max. 115.2 kbps
-Protocols supported
– Freeport: User-parameterizable telegram format for universal communication
– 3964(R) for improved transmission reliability
– Modbus RTU Master
– Modbus RTU Slave
– USS, implemented through instructions
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
SIPLUS CM PtP
Ordering data | Article No. |
---|---|
Communications moduleSIPLUS S7-1500 CM PtPRS 232 BA(Extended temperature range and exposure to environmental substances)Basic communications module with 1 RS 232 interface, Freeport, 3964(R) and USS protocols, 9-pin D-sub connector, max. 19.2 Kbps | 6AG1540-1AD00-7AA0 |
Communications moduleSIPLUS S7-1500 CM PtPRS 232 HF(Extended temperature range and exposure to environmental substances)High Feature communications module with 1 RS 232 interface, Freeport, 3964(R), USS and Modbus RTU protocols, 9-pin D-sub connector, max. 115.2 Kbps | 6AG1541-1AD00-7AB0 |
Communications moduleSIPLUS S7-1500 CM PtPRS 422/485 BA(Extended temperature range and exposure to environmental substances)Basic communications module with 1 interface RS 422/485, Freeport, 3964(R) and USS protocols, 15-pin D-sub socket, max. 19.2 Kbps | 6AG1540-1AB00-7AA0 |
Communications moduleSIPLUS S7-1500 CM PtPRS 422/485 HF(Extended temperature range and exposure to environmental substances)High Feature communications module with 1 RS 422/485 interface, Freeport, 3964(R), USS and Modbus RTU protocols, 15-pin D-sub socket, max. 115.2 Kbps | 6AG1541-1AB00-7AB0 |
AccessoriesSee SIMATIC S7-1500,CM PtP communications module, page 4/252 | — |
Technical specifications
หัวข้อ | 6AG1540-1AD00-7AA0(RS232 BA) | 6AG1541-1AD00-7AB0(RS232 HF) | 6AG1540-1AB00-7AA0(RS422/485 BA) | 6AG1541-1AB00-7AB0(RS422/485 HF) |
---|---|---|---|---|
Based on | 6ES7540-1AD00-0AA0 | 6ES7541-1AD00-0AB0 | 6ES7540-1AB00-0AA0 | 6ES7541-1AB00-0AB0 |
Ambient temperature during operationhorizontal installation, min. | -40 °C = Tmin (incl. condensation/frost);start-up @ -25 °C | -40 °C = Tmin (incl. condensation/frost);start-up @ -25 °C | -40 °C = Tmin (incl. condensation/frost);start-up @ -25 °C | -40 °C = Tmin (incl. condensation/frost);start-up @ -25 °C |
Ambient temperature during operationhorizontal installation, max. | 70 °C | 70 °C | 70 °C | 70 °C |
Ambient temperature during operationvertical installation, min. | -40 °C = Tmin;Startup @ -25 °C | -40 °C = Tmin;Startup @ -25 °C | -40 °C = Tmin;Startup @ -25 °C | -40 °C = Tmin;Startup @ -25 °C |
Ambient temperature during operationvertical installation, max. | 40 °C | 40 °C | 40 °C | 40 °C |
หัวข้อ | 6AG1540-1AD00-7AA0(RS232 BA) | 6AG1541-1AD00-7AB0(RS232 HF) | 6AG1540-1AB00-7AA0(RS422/485 BA) | 6AG1541-1AB00-7AB0(RS422/485 HF) |
---|---|---|---|---|
Altitude during operation relating to sea level• Installation altitude above sea level, max. | 5 000 m | 5 000 m | 5 000 m | 5 000 m |
Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at1 140 hPa … 795 hPa (-100 m … 2 000 m)Tmin … Tmax –10 K at795 hPa … 658 hPa (+2 000 m … +3 500 m)Tmin … Tmax –20 K at658 hPa … 540 hPa (+3 500 m … +5 000 m) | Tmin … Tmax at1 140 hPa … 795 hPa (-100 m … 2 000 m)Tmin … Tmax –10 K at795 hPa … 658 hPa (+2 000 m … +3 500 m)Tmin … Tmax –20 K at658 hPa … 540 hPa (+3 500 m … +5 000 m) | Tmin … Tmax at1 140 hPa … 795 hPa (-100 m … 2 000 m)Tmin … Tmax –10 K at795 hPa … 658 hPa (+2 000 m … +3 500 m)Tmin … Tmax –20 K at658 hPa … 540 hPa (+3 500 m … +5 000 m) | Tmin … Tmax at1 140 hPa … 795 hPa (-100 m … 2 000 m)Tmin … Tmax –10 K at795 hPa … 658 hPa (+2 000 m … +3 500 m)Tmin … Tmax –20 K at658 hPa … 540 hPa (+3 500 m … +5 000 m) |
Relative humidity• With condensation, tested in accordance with IEC 60068-2-38 | 100 % RH;incl. condensation/frost(commissioning under condensation conditions) | 100 % RH;incl. condensation/frost(commissioning under condensation conditions) | 100 % RH;incl. condensation/frost(commissioning under condensation conditions) | 100 % RH;incl. condensation/frost(commissioning under condensation conditions) |
Resistance• Coolants and lubricants | Yes; incl. diesel and oil | Yes; incl. diesel and oil | Yes; incl. diesel and oil | Yes; incl. diesel and oil |
Use in stationary industrial systems• biologically active substances | Yes; Class 3B2 mold, fungus(with exception of flowers) | Yes; Class 3B2 mold, fungus(with exception of flowers) | Yes; Class 3B2 mold, fungus(with exception of flowers) | Yes; Class 3B2 mold, fungus(with exception of flowers) |
Use in stationary industrial systems• chemically active substances | Yes; Class 3C4 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 3C4 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 3C4 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 3C4 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) |
Use in stationary industrial systems• mechanically active substances | Yes; Class 3S4 incl. sand, dust | Yes; Class 3S4 incl. sand, dust | Yes; Class 3S4 incl. sand, dust | Yes; Class 3S4 incl. sand, dust |
Use on ships/at sea• biologically active substances | Yes; Class 6B2 mold and fungal spores(excluding fungus); Class 6B3 on request | Yes; Class 6B2 mold and fungal spores(excluding fungus); Class 6B3 on request | Yes; Class 6B2 mold and fungal spores(excluding fungus); Class 6B3 on request | Yes; Class 6B2 mold and fungal spores(excluding fungus); Class 6B3 on request |
Use on ships/at sea• chemically active substances | Yes; Class 6C3 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 6C3 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 6C3 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) | Yes; Class 6C3 (RH < 75%)incl. salt spray acc. to EN 60068-2-52(severity degree 3) |
Use on ships/at sea• mechanically active substances | Yes; Class 6S3 incl. sand, dust | Yes; Class 6S3 incl. sand, dust | Yes; Class 6S3 incl. sand, dust | Yes; Class 6S3 incl. sand, dust |
Usage in industrial process technology | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) |
Usage in industrial process environments | Yes; Level GX group A/B(excluding trichlorethylene);harmful gas concentrations up to limits of EN 60721-3-3 class 3C4 permissible;level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B(excluding trichlorethylene);harmful gas concentrations up to limits of EN 60721-3-3 class 3C4 permissible;level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B(excluding trichlorethylene);harmful gas concentrations up to limits of EN 60721-3-3 class 3C4 permissible;level LC3 (salt spray) and level LB3 (oil) | Yes; Level GX group A/B(excluding trichlorethylene);harmful gas concentrations up to limits of EN 60721-3-3 class 3C4 permissible;level LC3 (salt spray) and level LB3 (oil) |
Remark | * The supplied plug covers are used during operation in the unassembled state | * The supplied plug covers are used during operation in the unassembled state | * The supplied plug covers are used during operation in the unassembled state | * The supplied plug covers are used during operation in the unassembled state |
Conformal coating | Yes; Class 2 for high reliabilityType 1 protectionYes; Conformal coating, possible during service lifeYes; Conformal coating, Class A | Yes; Class 2 for high reliabilityType 1 protectionYes; Conformal coating, possible during service lifeYes; Conformal coating, Class A | Yes; Class 2 for high reliabilityType 1 protectionYes; Conformal coating, possible during service lifeYes; Conformal coating, Class A | Yes; Class 2 for high reliabilityType 1 protectionYes; Conformal coating, possible during service lifeYes; Conformal coating, Class A |