วันจันทร์ - วันเสาร์ 8:00 น. - 17:00 น.

📞 📞

รุ่น KTP400, KTP700, KTP900 และ KTP1200

With their fully developed HMI basic functions, 2nd Generation
SIPLUS Basic Panels are the ideal entry-level series for simple
HMI applications.
The device family offers panels with 4″, 7″, 9″ and 12″ displays,
as well as combined key and touch operation.
The innovative high-resolution widescreen displays with
64 000 colors are also suitable for upright installation, and they
can be dimmed down to 100%. The innovative operator
interface with improved usability opens up a diverse range of
options thanks to new controls and graphics. The new USB
interface enables the connection of keyboard, mouse or
barcode scanner, and supports the simple archiving of data on a
USB flash drive.
The integrated Ethernet or RS 485/422 interface (version-specific)
enables simple connection to the controller.
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific
information was added.

หัวข้อรายละเอียด
SIPLUS HMI KTP400 Basic6AG1123-2DB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C
SIPLUS HMI KTP700 Basic6AG1123-2GB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C
SIPLUS HMI KTP700 Basic DP6AG1123-2GA03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C
SIPLUS HMI KTP900 Basic6AG1123-2JB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C
SIPLUS HMI KTP1200 Basic6AG1123-2MB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -10 … +50 °C
SIPLUS HMI KTP1200 Basic DP6AG1123-2MA03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -10 … +50 °C
AccessoriesSee catalog ST 80 / ST PC or Sieportal
หัวข้อ6AG1123-2DB03-2AX0(SIPLUS HMI KTP400 BASIC)6AG1123-2GB03-2AX0(SIPLUS HMI KTP700 BASIC)6AG1123-2GA03-2AX0(SIPLUS HMI KTP700 BASIC DP)
Ambient conditionsSuited for indoor useYesYesYes
Ambient conditionsSuited for outdoor useNoNoNo
Ambient temperature during operation(vertical installation)• Min.-20 °C-20 °C-20 °C
• Max.60 °C50 °C50 °C
Altitude during operation relating to sea level• Installation altitude above sea level, max.5 000 m5 000 m5 000 m
• Ambient air temperature-barometric pressure-altitudeTmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m)(เช่นเดียวกันกับซ้ายมือ)(เช่นเดียวกันกับซ้ายมือ)
Relative humidity100 %; RH incl. condensation/frost(no commissioning under condensation conditions)100 %; RH incl. condensation/frost(no commissioning under condensation conditions)100 %; RH incl. condensation/frost(no commissioning when condensation present), vertical mounting position
หัวข้อ6AG1123-2DB03-2AX0SIPLUS HMI KTP400 BASIC6AG1123-2GB03-2AX0SIPLUS HMI KTP700 BASIC6AG1123-2GA03-2AX0SIPLUS HMI KTP700 BASIC DP
Resistance – Coolants and lubricantsYes; incl. diesel and oil droplets in the airYes; incl. diesel and oil droplets in the airYes; incl. diesel and oil droplets in the air
Use in stationary industrial systems – Biologically active substancesYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request
Use in stationary industrial systems – Chemically active substancesYes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3Yes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3Yes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3
Use in stationary industrial systems – Mechanically active substancesYes; Class 3S1 incl. sand, dust *Yes; Class 3S1 incl. sand, dust *Yes; Class 3S1 incl. sand, dust *
Use on ships/offshore – Biologically active substancesYes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on requestYes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on requestYes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on request
Use on ships/offshore – Chemically active substancesYes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3Yes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3Yes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3
Use on ships/offshore – Mechanically active substancesYes; Class 6S3 incl. sand, dust *Yes; Class 6S3 incl. sand, dust *Yes; Class 6S3 incl. sand, dust *
Use in industrial process technology – Chemically active substancesYes; Class 3 (excl. trichlorethylene)Yes; Class 3 (excl. trichlorethylene)Yes; Class 3 (excl. trichlorethylene)
Use in industrial process technology – Environmental conditions acc. ANSI/ISA-71.04Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil)Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil)Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil)
RemarkThe supplied plug covers must remain in place when unused interfaces during operation!(เหมือนซ้าย)(เหมือนซ้าย)
Conformal coating – ClassYes; Class 2 for high reliabilityYes; Class 2 for high reliabilityYes; Class 2 for high reliability
Conformal coating – Protection against voltageYes; Type 1 protectionYes; Type 1 protectionYes; Type 1 protection
Conformal coating – Military testingYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service life
Conformal coating – Class AYes; Conformal coating, Class AYes; Conformal coating, Class AYes; Conformal coating, Class A
หัวข้อ6AG1123-2JB03-2AX0SIPLUS HMI KTP900 BASIC6AG1123-2MB03-2AX0SIPLUS HMI KTP1200 BASIC6AG1123-2MA03-2AX0SIPLUS HMI KTP1200 BASIC DP
Ambient conditionsSuited for indoor useYesYesYes
Ambient conditionsSuited for outdoor useNoNoNo
Ambient temperature during operationOperation (vertical installation) – For vertical installation, min.-20 °C-10 °C = Tmin-10 °C = Tmin
– For vertical installation, max.50 °C50 °C50 °C
หัวข้อ6AG1123-2JB03-2AX0SIPLUS HMI KTP900 BASIC6AG1123-2MB03-2AX0SIPLUS HMI KTP1200 BASIC6AG1123-2MA03-2AX0SIPLUS HMI KTP1200 BASIC DP
Altitude during operation relating to sea level• Installation altitude above sea level, max.5 000 m5 000 m5 000 m
• Ambient air temperature-barometric pressure-altitudeTmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m)Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m)Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m)
Relative humidity100 % RH incl. condensation/frost (no commissioning under condensation conditions)100 % RH incl. condensation/frost (no commissioning in dewed state), horizontal installation100 % RH incl. condensation/frost (no commissioning when condensation present), vertical mounting position
Resistance – Coolants and lubricantsYes; incl. diesel and oil droplets in the airYes; incl. diesel and oil droplets in the airYes; incl. diesel and oil droplets in the air
Use in stationary industrial systems – Biologically active substancesYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on requestYes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request
Use in stationary industrial systems – Chemically active substancesYes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3Yes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3Yes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3
Use in stationary industrial systems – Mechanically active substancesYes; Class 3S4 incl. sand, dust *Yes; Class 3S4 incl. sand, dust *Yes; Class 3S4 incl. sand, dust *
Use on ships/at sea – Biologically active substancesYes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on requestYes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on requestYes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on request
Use on ships/at sea – Chemically active substancesYes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3)(Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3)Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3)
Use on ships/at sea – Mechanically active substancesYes; Class 6S3 incl. sand, dust *Yes; Class 6S3 incl. sand, dust *Yes; Class 6S3 incl. sand, dust *
Usage in industrial process technology – Chemically active substancesYes; Class 3 (excluding trichlorethylene)Yes; Class 3 (excluding trichlorethylene)Yes; Class 3 (excluding trichlorethylene)
Usage in industrial process technology – Environmental conditions (ANSI/ISA-71.04)Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil)Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil)Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil)
RemarkThe supplied plug covers must remain in place over the unused interfaces during operation!The supplied plug covers must remain in place over the unused interfaces during operation!The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating – Coatings for printed circuit board assembliesYes; Class 2 for high reliabilityYes; Class 2 for high reliabilityYes; Class 2 for high reliability
Conformal coating – Protection against voltageYes; Type 1 protectionYes; Type 1 protectionYes; Type 1 protection
Conformal coating – Military testingYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service lifeYes; Discoloration of coating possible during service life
Conformal coating – Class AYes; Conformal coating, Class AYes; Conformal coating, Class AYes; Conformal coating, Class A

สินค้าที่เกี่ยวข้อง

ติดต่อสอบถามเพิ่มเติม

โทรติดต่อ

085-838-2423
085-150-5506
062-381-5341

อีเมล

sale@enscigroup.com

เปิดทำการ

จันทร์ - เสาร์
08.00 - 17.00 น.

สอบถามผ่าน Social Media

SIPLUS HMI Basic Panels จาก Siemens – รุ่น KTP400, KTP700, KTP900 และ KTP1200 สำหรับสภาพแวดล้อมอุตสาหกรรม