รุ่น KTP400, KTP700, KTP900 และ KTP1200
With their fully developed HMI basic functions, 2nd Generation
SIPLUS Basic Panels are the ideal entry-level series for simple
HMI applications.
The device family offers panels with 4″, 7″, 9″ and 12″ displays,
as well as combined key and touch operation.
The innovative high-resolution widescreen displays with
64 000 colors are also suitable for upright installation, and they
can be dimmed down to 100%. The innovative operator
interface with improved usability opens up a diverse range of
options thanks to new controls and graphics. The new USB
interface enables the connection of keyboard, mouse or
barcode scanner, and supports the simple archiving of data on a
USB flash drive.
The integrated Ethernet or RS 485/422 interface (version-specific)
enables simple connection to the controller.
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific
information was added.
| หัวข้อ | รายละเอียด |
|---|---|
| SIPLUS HMI KTP400 Basic | 6AG1123-2DB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C |
| SIPLUS HMI KTP700 Basic | 6AG1123-2GB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C |
| SIPLUS HMI KTP700 Basic DP | 6AG1123-2GA03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C |
| SIPLUS HMI KTP900 Basic | 6AG1123-2JB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -20 … +60 °C |
| SIPLUS HMI KTP1200 Basic | 6AG1123-2MB03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -10 … +50 °C |
| SIPLUS HMI KTP1200 Basic DP | 6AG1123-2MA03-2AX0 For areas with extreme exposure to environmental substances (conformal coating); ambient temperature -10 … +50 °C |
| Accessories | See catalog ST 80 / ST PC or Sieportal |
| หัวข้อ | 6AG1123-2DB03-2AX0(SIPLUS HMI KTP400 BASIC) | 6AG1123-2GB03-2AX0(SIPLUS HMI KTP700 BASIC) | 6AG1123-2GA03-2AX0(SIPLUS HMI KTP700 BASIC DP) |
|---|---|---|---|
| Ambient conditionsSuited for indoor use | Yes | Yes | Yes |
| Ambient conditionsSuited for outdoor use | No | No | No |
| Ambient temperature during operation(vertical installation)• Min. | -20 °C | -20 °C | -20 °C |
| • Max. | 60 °C | 50 °C | 50 °C |
| Altitude during operation relating to sea level• Installation altitude above sea level, max. | 5 000 m | 5 000 m | 5 000 m |
| • Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m) | (เช่นเดียวกันกับซ้ายมือ) | (เช่นเดียวกันกับซ้ายมือ) |
| Relative humidity | 100 %; RH incl. condensation/frost(no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost(no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost(no commissioning when condensation present), vertical mounting position |
| หัวข้อ | 6AG1123-2DB03-2AX0SIPLUS HMI KTP400 BASIC | 6AG1123-2GB03-2AX0SIPLUS HMI KTP700 BASIC | 6AG1123-2GA03-2AX0SIPLUS HMI KTP700 BASIC DP |
|---|---|---|---|
| Resistance – Coolants and lubricants | Yes; incl. diesel and oil droplets in the air | Yes; incl. diesel and oil droplets in the air | Yes; incl. diesel and oil droplets in the air |
| Use in stationary industrial systems – Biologically active substances | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request |
| Use in stationary industrial systems – Chemically active substances | Yes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 | Yes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 | Yes; Class 3C4 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 |
| Use in stationary industrial systems – Mechanically active substances | Yes; Class 3S1 incl. sand, dust * | Yes; Class 3S1 incl. sand, dust * | Yes; Class 3S1 incl. sand, dust * |
| Use on ships/offshore – Biologically active substances | Yes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on request | Yes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on request | Yes; Class 6B2 mold and fungus (excl. fauna); Class 6B3 on request |
| Use on ships/offshore – Chemically active substances | Yes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 | Yes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 | Yes; Class 6C3 (RH <75 %) incl. salt spray; EN 60068-2-52 severity 3 |
| Use on ships/offshore – Mechanically active substances | Yes; Class 6S3 incl. sand, dust * | Yes; Class 6S3 incl. sand, dust * | Yes; Class 6S3 incl. sand, dust * |
| Use in industrial process technology – Chemically active substances | Yes; Class 3 (excl. trichlorethylene) | Yes; Class 3 (excl. trichlorethylene) | Yes; Class 3 (excl. trichlorethylene) |
| Use in industrial process technology – Environmental conditions acc. ANSI/ISA-71.04 | Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil) | Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil) | Yes; Level G1, G2, G3 (Class 3C4 permissible); Level L1, L2, L3 (oil) |
| Remark | The supplied plug covers must remain in place when unused interfaces during operation! | (เหมือนซ้าย) | (เหมือนซ้าย) |
| Conformal coating – Class | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability |
| Conformal coating – Protection against voltage | Yes; Type 1 protection | Yes; Type 1 protection | Yes; Type 1 protection |
| Conformal coating – Military testing | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life |
| Conformal coating – Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A |
| หัวข้อ | 6AG1123-2JB03-2AX0SIPLUS HMI KTP900 BASIC | 6AG1123-2MB03-2AX0SIPLUS HMI KTP1200 BASIC | 6AG1123-2MA03-2AX0SIPLUS HMI KTP1200 BASIC DP |
|---|---|---|---|
| Ambient conditionsSuited for indoor use | Yes | Yes | Yes |
| Ambient conditionsSuited for outdoor use | No | No | No |
| Ambient temperature during operationOperation (vertical installation) – For vertical installation, min. | -20 °C | -10 °C = Tmin | -10 °C = Tmin |
| – For vertical installation, max. | 50 °C | 50 °C | 50 °C |
| หัวข้อ | 6AG1123-2JB03-2AX0SIPLUS HMI KTP900 BASIC | 6AG1123-2MB03-2AX0SIPLUS HMI KTP1200 BASIC | 6AG1123-2MA03-2AX0SIPLUS HMI KTP1200 BASIC DP |
|---|---|---|---|
| Altitude during operation relating to sea level• Installation altitude above sea level, max. | 5 000 m | 5 000 m | 5 000 m |
| • Ambient air temperature-barometric pressure-altitude | Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m) | Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m) | Tmin … Tmax at 1 140 hPa … 795 hPa(-1 000 m … +2 000 m) // Tmin … (Tmax -10 K) at 795 hPa … 658 hPa(+2 000 m … +3 500 m) // Tmin … (Tmax -20 K) at 658 hPa … 540 hPa(+3 500 m … +5 000 m) |
| Relative humidity | 100 % RH incl. condensation/frost (no commissioning under condensation conditions) | 100 % RH incl. condensation/frost (no commissioning in dewed state), horizontal installation | 100 % RH incl. condensation/frost (no commissioning when condensation present), vertical mounting position |
| Resistance – Coolants and lubricants | Yes; incl. diesel and oil droplets in the air | Yes; incl. diesel and oil droplets in the air | Yes; incl. diesel and oil droplets in the air |
| Use in stationary industrial systems – Biologically active substances | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request | Yes; Class 3B2 mold, fungus, dry spores (excl. fauna); Class 3B3 on request |
| Use in stationary industrial systems – Chemically active substances | Yes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray; EN 60068-2-52 severity degree 3 |
| Use in stationary industrial systems – Mechanically active substances | Yes; Class 3S4 incl. sand, dust * | Yes; Class 3S4 incl. sand, dust * | Yes; Class 3S4 incl. sand, dust * |
| Use on ships/at sea – Biologically active substances | Yes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on request | Yes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on request | Yes; Class 6B2 mold and fungal spores (excl. fauna); Class 6B3 on request |
| Use on ships/at sea – Chemically active substances | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3) | (Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3) | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3) |
| Use on ships/at sea – Mechanically active substances | Yes; Class 6S3 incl. sand, dust * | Yes; Class 6S3 incl. sand, dust * | Yes; Class 6S3 incl. sand, dust * |
| Usage in industrial process technology – Chemically active substances | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) | Yes; Class 3 (excluding trichlorethylene) |
| Usage in industrial process technology – Environmental conditions (ANSI/ISA-71.04) | Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil) | Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil) | Yes; Level G1–G3 (Class 3C4 permissible), level L1–L3 (oil) |
| Remark | The supplied plug covers must remain in place over the unused interfaces during operation! | The supplied plug covers must remain in place over the unused interfaces during operation! | The supplied plug covers must remain in place over the unused interfaces during operation! |
| Conformal coating – Coatings for printed circuit board assemblies | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability | Yes; Class 2 for high reliability |
| Conformal coating – Protection against voltage | Yes; Type 1 protection | Yes; Type 1 protection | Yes; Type 1 protection |
| Conformal coating – Military testing | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life | Yes; Discoloration of coating possible during service life |
| Conformal coating – Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A | Yes; Conformal coating, Class A |