ㆍCommunication module for connecting up to 8 IO-Link devices (three-wire connection) or 8 standandard sensors
ㆍ Can be used directly downstream of an S7-1500 CPU or distributed in ET 200MP via PROFINET or PROFIBUS
ㆍ Powerful diagnostics functions facilitate preventive maintenance to avoid plant standstills
ㆍEasy replacement of sensors/actuators without time-consuming parameter assignment
หัวข้อ | รายละเอียด |
---|---|
Ordering data | |
S7-1500, CM 8xIO-Link, communications module IO-Link Master V1.1 | 6ES7547-1JF00-0AB0order front connectors (screw terminals or push-in) separately |
Accessories | |
SIMATIC Manual Collection on DVD, 5 languages | 6ES7998-8XC01-8YE0All manuals for S7-1200/1500/200/300/400, LOGO!, SIMATIC DP, PC, PG, STEP 7, Engineering SW, Runtime SW, SIMATIC HMI, SIMATIC NET, SIMATIC IDENT |
SIMATIC Manual Collection on DVD, 5 languages (Software Update Service) | 6ES7998-8XC01-8YE2Software Update Service, under this contract, you receive all software versions for one year. The contract is automatically extended for one more year unless it is canceled three months before expiration. Delivery and service period: 1 year from date of invoice |
หัวข้อ | รายละเอียด |
---|---|
Article number | 6ES7547-1JF00-0AB0S7-1500, CM 8xIO-Link |
General information | |
Product type designation | CM 8xIO-Link |
Product function | ● I&M dataYes; I&M0 to I&M3 |
Engineering with | ● STEP 7 TIA Portal configurable / integrated from versionV15.1 with HSP 274● STEP 7 configurable / integrated from versionConfigurable via GSD file● PROFIBUS from GSD version / GSD revisionGSD as of Revision 5● PROFINET from GSD version / GSD revisionGSDML V2.34 |
Supply voltage | |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Encoder supply | |
Number of outputs | 8 |
Output current | |
Rated value | 1 A; 4 A total current per module |
24 V encoder supply | |
Short-circuit protection | Yes; per channel, electronic |
IO-Link | |
Number of ports | 8 |
● of which simultaneously controllable | 8 |
IO-Link protocol 1.0 | Yes |
IO-Link protocol 1.1 | Yes |
Cycle time, min. | 2 ms |
Size of process data, input per port | 33 byte; max. |
Size of process data, input per module | 240 byte; max. |
Size of process data, output per port | 32 byte; max. |
Size of process data, output per module | 240 byte; max. |
Memory size for device parameter | 2 kbyte; for each port |
Master backup | Yes |
Configuration without S7-PCT | Yes |
Cable length unshielded, max. | 20 m |
Operating modes | |
● IO-Link | Yes |
● DI | Yes |
● DE | Yes |
Time Based IO | |
● TIO IO-Link IN | No |
● TIO IO-Link OUT | No |
● TIO IO-Link IN/OUT | No |
Connection of IO-Link devices | |
● Port type A | Yes |
● Port type B | Yes; 24 V DC via external terminal |
S7-1500, CM 8xIO-Link,communications module IO-Link Master V1.1 | 6ES7547-1JF00-0AB0order front connectors (screw terminals or push-in) separately |
หัวข้อ | รายละเอียด |
---|---|
Article number | 6ES7547-1JF00-0AB0S7-1500, CM 8xIO-Link |
Interrupts/diagnostics/status information | |
Alarms | ● Diagnostic alarmYes; The port diagnosis is available in the IO-Link mode only. |
Diagnoses | ● Monitoring the supply voltage: Yes● Wire-break: Yes● Short-circuit: Yes● Group error: Yes |
Diagnostics indication LED | ● Monitoring of the supply voltage (PWR-LED): Yes; green LED● Channel status display for channel diagnostics: Yes; green LED / Yes; red LED● for module diagnostics: Yes; red LED |
Potential separation | |
Potential separation channels | ● between the channels and backplane bus: Yes |
Ambient conditions | |
Ambient temperature during operation | ● horizontal installation, min.: 0 °C● horizontal installation, max.: 60 °C; Observe derating● vertical installation, min.: 0 °C● vertical installation, max.: 40 °C; Observe derating |
Altitude during operation relating to sea level | ● Installation altitude above sea level, max.: 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | ● Width: 35 mm● Height: 147 mm● Depth: 129 mm |