MasterPact MTZ Active MTZ2 fixed for MicroLogic X,
3P 1250A 66kA/415VAC
This device is a breaker frame for MasterPacT MTZ with Micrologic Active last generation of high current air circuit breakers. MasterPacT MTZ2 12H1 is a 3 poles breaker frame in fixed version. The rated current is 1250A. The breaking capacity (Icu) is 66kA rms at 440VAC 50/60Hz. This breaker frame is compatible with MicroLogic Active control unit which has also to be ordered separately. MasterPacT MTZ Active combines real-time information and ease of use to enable fast mitigation of outage events. MasterPacT MTZ Active is designed to achieve new levels of uptime and agility. MicroLogic Active control units embeds features for protection, measurement, communication, maintenance and diagnosis. The dimensions are 422mm (W) x 352mm (H) x 300mm (D), the weight is approximately 50kg. MasterPacT MTZ Active is compliant with international standards IEC 60947-1 and IEC 60947-2. MasterPacT MTZ Active circuit breakers are part of the Active Panel solution made possible by Schneider Electric’s EcoStruxure Power architecture. Green packaging eliminates single-use plastics and features 100% recycled and recyclable cardboard. Transformer efficiency data helps inform actions to save energy and reduce CO2 emissions.
Specifications
| Range | MasterPacT |
|---|---|
| Product name | MasterPacT MTZ2 Active |
| Product or component type | Circuit breaker |
| Device short name | MTZ2 12 H1 |
| Device application | Power distribution protection |
| Poles description | 3P |
| Control unit | Without control unit |
| Product compatibility | control unit MicroLogic Active 1.0 E control unit MicroLogic Active 1.0 EP control unit MicroLogic Active 2.0 A control unit MicroLogic Active 2.0 AP control unit MicroLogic Active 2.0 E control unit MicroLogic Active 2.0 EP control unit MicroLogic Active 5.0 A control unit MicroLogic Active 5.0 AP control unit MicroLogic Active 5.0 E control unit MicroLogic Active 5.0 EP control unit MicroLogic Active 6.0 A control unit MicroLogic Active 6.0 AP control unit MicroLogic Active 6.0 E control unit MicroLogic Active 6.0 EP |
| [In] rated current | 1250 A at 40 °C |
| Performance type | H1 66 kA 440 V AC |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Selectivity category | Category B |
| Control type | Push-button |
| Mounting mode | Fixed |
| [Icu] rated ultimate short-circuit breaking capacity | 66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 525 V AC 50/60 Hz 66 kA at 690 V AC 50/60 Hz |
|---|---|
| [Ics] rated service short-circuit breaking capacity | 66 kA at 220/415 V AC 50/60 Hz 66 kA at 440 V AC 50/60 Hz 66 kA at 525 V AC 50/60 Hz 66 kA at 690 V AC 50/60 Hz |
| [Icw] rated short-time withstand current | 66 kA 0.5 s 66 kA 1 s 36 kA 3 s |
| [Icm] rated short-circuit making capacity | 145 kA 220/415 V AC at 50/60 Hz 145 kA 440 V AC at 50/60 Hz 145 kA 525 V AC at 50/60 Hz 145 kA 690 V AC at 50/60 Hz |
| Sensor rating | 630A, 800A, 1000A, 1250A |
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 12 kV |
| Power dissipation in W | 100 W |
| Power dissipation per pole | 33.3 W |
| Maximum breaking time | 25 ms |
| Maximum closing response time | 70 ms |
| Mounting support | Base plate Rails |
| Upside connection | Front Rear |
| Downside connection | Front Rear |
| Connection pitch | 115 mm |
| Mechanical durability | 25,000 cycles with maintenance |
| Electrical durability | 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Height (H) | 352 mm |
| Width (W) | 422 mm |
| Depth (D) | 297 mm |
| Net weight | 50 kg |
| Standards | EN/IEC 60947-1 EN/IEC 60947-2 |
| Product certifications | CE CCC EAC |
| IP degree of protection | IP3X conforming to EN/IEC 60529 |
|---|---|
| IK degree of protection | IK07 conforming to EN 50102 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -25…70 °C |
| Temperature derating table | 40 °C ( 1250 A 45 °C ( 1250 A 50 °C ( 1250 A 55 °C ( 1250 A 60 °C ( 1250 A 65 °C ) ( 1250 A 70 °C ( 1250 A |
| Ambient air temperature for storage | -40…85 °C |
| Operating altitude | 0…2000 m without derating 2000 m…5000 m with derating |












