SCHNEIDER Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,630A,220V AC coil
LC1E630M7
รายละเอียด
Easy TeSys Control contactor 3 poles for motor applications up to 630A 400kW@440V. It provides a 220V 50/60Hz AC coil, without built-in auxiliary contacts, power and control connections by screw clamp terminals. 309mm width for standard operating rates up to 1200 cycles per hour. It procures standard reliability and durability with 0.6 Mcycles electrical durability AC-3 and 4 Mcycles mechanical durability. It can cover -5°C to 55°C working temperature and mounted by DIN-rail, No derating up to 3000m altitude. Multi-standards certified (IEC, CCC, EAC) and Green Premium compliant (RoHs/Reach)
ข้อมูลจำเพาะ
Range | Easy TeSys |
---|---|
Range of product | Easy TeSys Control |
Product or component type | Contactor |
Device short name | LC1E |
Contactor application | Motor control Resistive load |
Utilisation category | AC-3 AC-3e AC-1 |
Poles description | 3P |
[Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
[Ie] rated operational current | 630 A (at <55 °C) at <= 440 V AC AC-3 for power circuit 500 A (at <55 °C) at <= 440 V AC AC-3e for power circuit 1000 A (at <40 °C) at <= 440 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
Motor power kW | 185 kW at 220…230 V AC 50/60 Hz 335 kW at 380…400 V 375 kW at 415 V 400 kW at 440 V 400 kW at 500 V 450 kW at 660…690 V |
---|---|
Pole contact composition | 3 NO |
[Ith] conventional free air thermal current | 1000 A (at 40 °C) for power circuit |
Irms rated making capacity | 6300 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity | 5040 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current | 5050 A 40 °C – 10 s for power circuit |
Associated fuse rating | 10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1 800 A gG at <= 690 V coordination type 1 for power circuit |
Average impedance | 0.12 mOhm – Ith 1000 A 50 Hz for power circuit |
Power dissipation per pole | 48 W AC-3 120 W AC-1 |
[Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
Overvoltage category | III |
pollution degree | 3 |
[Uimp] rated impulse withstand voltage | 8 kV coil not connected to the power circuit conforming to IEC 60947 |
Mechanical durability | 4000000 cycles |
Electrical durability | 200000 cycles AC-1 600000 cycles AC-3 |
Control circuit type | AC at 50/60 Hz |
Control circuit voltage limits | 0.85…1.1 Uc (-5…55 °C):operational 50/60 Hz 0.25…0.5 Uc (-5…55 °C):drop-out 50/60 Hz |
Inrush power in VA | 1650 VA 50 Hz cos phi 0.9 (at 20 °C) 1650 VA 60 Hz cos phi 0.9 (at 20 °C) |
Hold-in power consumption in VA | 22 VA 50 Hz cos phi 0.9 (at 20 °C) 22 VA 60 Hz cos phi 0.9 (at 20 °C) |
Heat dissipation | 20 W for control circuit 20 W |
Operating time | 40…80 ms on closing 100…200 ms on opening |
Maximum operating rate | 1200 cyc/h 55 °C |
Connections – terminals | Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid without cable end Power circuit: cable with lug 2 Power circuit: bars 2 – busbar cross section: 60 x 5 mm |
Tightening torque | Control circuit: 1.2 N.m Power circuit: 58 N.m |
Minimum switching voltage | 17 V for control circuit |
Minimum switching current | 5 mA for control circuit |
Insulation resistance | > 10 MOhm for control circuit |
Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact 1.5 ms on de-energisation guaranteed between NC and NO contact |
Mounting support | Plate |
Standards | IEC 60947-5-1 IEC 60947-4-1 IEC 60947-1 |
---|---|
Product certifications | EAC CE |
IP degree of protection | IP00 conforming to IEC 60529 |
Permissible ambient air temperature around the device | -20…70 °C at Uc -60…80 °C storage -5…55 °C operation |
Operating altitude | 3000 m without derating |
Fire resistance | 850 °C conforming to IEC 60695-2-1 |
Mechanical robustness | Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms) Vibrations contactor open (2 Gn, 5…300 Hz) Vibrations contactor closed (4 Gn, 5…300 Hz) |
Height | 304 mm |
Width | 309 mm |
Depth | 255 mm |
Net weight | 18.6 kg |
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 30.000 cm |
Package 1 Width | 46.500 cm |
Package 1 Length | 36.500 cm |
Package 1 Weight | 18.847 kg |
Unit Type of Package 2 | P06 |
Number of Units in Package 2 | 4 |
Package 2 Height | 75.000 cm |
Package 2 Width | 60.000 cm |
Package 2 Length | 80.000 cm |
Package 2 Weight | 83.888 kg |