Manual transfer switch, รุ่น GoPact MTS 200, 4 โพล, 200A, 415VAC 50/60Hz, extended rotary handle, open transition
| Range of product | GoPact MTS |
|---|---|
| Product or component type | Manual transfer switch |
| Product name | GoPact MTS 200 |
| Device application | Change source of supply |
| Frame size | 200 |
| Suitability for isolation | Yes conforming to IEC 60947-3 |
| Transfer switch class | PC |
| Poles description | 4P |
| [Ie] rated operational current | AC-21A 200 A conforming to IEC 60947-3 AC-22A 200 A conforming to IEC 60947-3 AC-23A 200 A conforming to IEC 60947-3 AC-31B 200 A conforming to IEC 60947-6-1 AC-32B 200 A conforming to IEC 60947-6-1 |
| [Ith] conventional free air thermal current | 200 A at 40 °C |
| [Ithe] conventional enclosed thermal current | 200 A (40 °C |
| Rated operational power in W | 85 kW AC-23A conforming to IEC 60947-3 |
| [Ue] rated operational voltage | 415 V AC 50/60 Hz |
| Breaking capacity | 1600 A AC-23A |
| Rated making capacity | 2000 A AC-23A |
| Control type | Extended rotary handle |
| Operating mode | Manual |
| Contact position indicator | Yes |
| Mechanical interlocking | With mechanical interlocking |
| Locking options description | Padlocking in OFF position 1 to 3 padlocks |
| [Ui] rated insulation voltage | 1000 V AC |
|---|---|
| [Uimp] rated impulse withstand voltage | 12 kV |
| [Icm] rated short-circuit making capacity | 14 kA peak |
| [Icw] rated short-time withstand current | 8 kA during 1 s conforming to IEC 60947-4-3 18 kA during 0.2 s conforming to IEC 60947-4-3 10 kA during 0.1 s conforming to IEC 60947-6-1 |
| Number of contact position | 3 |
| Mounting mode | Fixed |
| Mounting support | Backplate |
| Connections – terminals | 1 cable with lug wire size 150 mm² |
| Tightening torque | 10 N.m |
| Mechanical durability | 16000 cycles |
| Electrical durability | 1000 cycles 415 V |
| Width | 210 mm |
| Height | 211 mm |
| Depth | Without handle 154 mm With handle 267 mm |
| Net weight | 4 kg |
| Standards | IEC 60947-3 IEC 60947-6-1 |
| Product certifications | IECEE CB Scheme |
| Electrical shock protection class | Class II |
|---|---|
| IP degree of protection | IP54 front face conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60664-1 |
| Ambient air temperature for operation | -5…55 °C |
| Temperature derating table | 40 °C ( 200 A 45 °C ( 200 A 50 °C ( 200 A 55 °C ( 190 A |
| Ambient air temperature for storage | -25…85 °C |
| Operating altitude | 2000 m 100 % of In 3000 m 96 % of In 4000 m 93 % of In 5000 m 89 % of In |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of Units in Package 1 | 1 |
| Package 1 Height | 33.3 cm |
| Package 1 Width | 22.6 cm |
| Package 1 Length | 26 cm |
| Package 1 Weight | 6.7 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 88.4 cm |
| Package 2 Width | 60 cm |
| Package 2 Length | 80 cm |
| Package 2 Weight | 267.6 kg |