FRANKE – GMKPc800II POWER FACTOR CONTROLLER (PFC)

GMKPc800II PFC 14 STEPS ( CAN MEASURE INDIVIDUAL HARMONIC ) SIZE 144×144 mm. ( CUT 138×138 mm. )

Reactive power compensation plants are used to decrease the load of cables and power distributions caused by inductive currents and to save reactive power costs. The power factor controller is a main part of such a plant and connects or disconnects capacitor stages automatically. The series GMKPc power factor controllers are suitable for the use in conventional or special dynamic reactive power compensation systems and a mixed operation is possible as well.

Features

  • Micro-processor based.
  • Digital power factor display.
  • Programmable switching sequence (optimized) (auto, custom or preset).
  • LED indication for individual step. 5 Auto manual operation.
  • Automatic detection of C.T. polarity.
  • Automatic detection of C/K value.
  • Secondary current / power factor info display、voltage / frequency info display.
  • THD / individual harmonic info display. (3th to11th harmonics display)
  • Alarm output. (THD, frequency, under/over compensate, over voltage).
  • Integrated timer-controlled exhaust fan output.
  • Programmable THD cut-off.
  • Keypad lock (software programmable).
  • Flush mount more than 14 steps.

 

Sepcification

Specification  Details
Power Supply (Un) 220VAC ±10% or other on request
Rated Current (In) ../5A (same phase with power supply)
Working Current (C/K) 0.02 – 10.0
Operating Frequency (Hz) 45 – 65
Power Factor Setting 0.85 – 0.95
Output Relay/Alarm/Fan (Qn) 5A / 250VAC
System Protection (THD,U) Harmonic THD off: 20 – 100%, Voltage off: 240 – 270V
Re-connection Time (Sec.) 1 – 250
Step Programme P0–P6: Liner and 1:1:1:1:1:1; 1:2:2:2:2; 1:1:2:2:2:2; 1:2:4:4:4:4; 1:1:2:2:4

 

Paraments setting & section

Specification Details
C/K Auto/Manual sensitivity setting = 1st cap. Bank (Kvar) + CT ratio
Target Cosδ Power factor to be achieved
No. Connected Steps The number of capacitor bank connected to be network
Switching Program Custom program/Auto/7 selectable switching programs
Switching Time Capacitor bank switching delay time (sec.)
Re-Connection Time Re-connection delay time (sec.)
Voltage (V) Over-voltage limit
THD>(%) alarm & voltage Total harmonic distortion limit
CosΦ Displacement power factor (Default Mode)
I secondary (A) Real-time secondary CT current (ampere) press [select] to view actual power factor
Voltage info Real-time line voltage value press [select] to view frequency (Hz) value
THD (%) Total harmonic distortion (current: load > 0.30A)
(Current & Voltage) Press [select] to view individual nth odd harmonic amplitude up to 11th order
Operation hr Operation hour × 1000 hours (e.g. 0.01 × 1000 = 10 hours in operation)
Alarm info Alarm warnings

 

Electric connection

 

Mounting draw of GMKPc800II controller

 

Plane description