031607 Model code: P3-63/EA/SVB
Eaton Moeller® series P3 Main switch, P3, 63 A, flush mounting, 3 pole, Emergency switching off function, With red rotary handle and yellow locking ring, Lockable in the 0 (Off) position.
General specifications
Product Name |
Eaton Moeller® series P3 Main switch
|
Catalog Number |
031607
|
Model Code |
P3-63/EA/SVB
|
EAN |
4015080316077
|
Product Length/Depth |
128 mm
|
Product Height |
102 mm
|
Product Width |
87 mm
|
Product Weight |
0.426 kg
|
Certifications |
UL
UL Category Control No.: NLRV IEC/EN 60947 CSA Class No.: 3211-05 CSA-C22.2 No. 60947-4-1-14 CSA File No.: 012528 UL 60947-4-1 CE UL File No.: E36332 VDE 0660 IEC/EN 60204 CSA-C22.2 No. 94 CSA IEC/EN 60947-3 |
Catalog Notes |
Rated Short-time Withstand Current (Icw) for a time of 1 second
|
Product specifications
Product Category |
Main switch
|
Features |
Version as emergency stop installation
Version as maintenance-/service switch Version as main switch |
Actuator color |
Red
|
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
|
10.11 Short-circuit rating |
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
|
10.12 Electromagnetic compatibility |
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
|
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
|
10.2.2 Corrosion resistance |
Meets the product standard’s requirements.
|
10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard’s requirements.
|
10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard’s requirements.
|
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects |
Meets the product standard’s requirements.
|
10.2.4 Resistance to ultra-violet (UV) radiation |
UV resistance only in connection with protective shield.
|
10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.2.7 Inscriptions |
Meets the product standard’s requirements.
|
10.3 Degree of protection of assemblies |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.4 Clearances and creepage distances |
Meets the product standard’s requirements.
|
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated.
|
10.7 Internal electrical circuits and connections |
Is the panel builder’s responsibility.
|
10.8 Connections for external conductors |
Is the panel builder’s responsibility.
|
10.9.2 Power-frequency electric strength |
Is the panel builder’s responsibility.
|
10.9.3 Impulse withstand voltage |
Is the panel builder’s responsibility.
|
10.9.4 Testing of enclosures made of insulating material |
Is the panel builder’s responsibility.
|
Fitted with: |
Red rotary handle and yellow locking ring
|
Operating frequency |
1200 Operations/h
|
Pollution degree |
3
|
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30 |
Rated impulse withstand voltage (Uimp) |
6000 V AC
|
Rated permanent current at AC-21, 400 V |
63 A
|
Rated permanent current at AC-23, 400 V |
63 A
|
Rated uninterrupted current (Iu) |
63 A
|
Static heat dissipation, non-current-dependent Pvs |
0 W
|
Switching power at 400 V |
30 kW
|
Voltage per contact pair in series |
60 V
|
Accessories |
Auxiliary contact or neutral conductor fitted by user.
|
Rated operational power at AC-3, 500 V, 50 Hz |
30 kW
|
Device construction |
Built-in device fixed built-in technique
|
Rated short-time withstand current (Icw) |
1.26 kA
|
Electrical connection type of main circuit |
Screw connection
|
Mounting position |
As required
|
Actuator type |
Door coupling rotary drive
|
Ambient operating temperature – max |
50 °C
|
Ambient operating temperature – min |
-25 °C
|
Ambient operating temperature (enclosed) – max |
40 °C
|
Ambient operating temperature (enclosed) – min |
-25 °C
|
Assigned motor power at 115/120 V, 60 Hz, 1-phase |
3 HP
|
Assigned motor power at 200/208 V, 60 Hz, 1-phase |
7.5 HP
|
Assigned motor power at 200/208 V, 60 Hz, 3-phase |
15 HP
|
Assigned motor power at 230/240 V, 60 Hz, 1-phase |
10 HP
|
Assigned motor power at 230/240 V, 60 Hz, 3-phase |
15 HP
|
Assigned motor power at 460/480 V, 60 Hz, 3-phase |
40 HP
|
Assigned motor power at 575/600 V, 60 Hz, 3-phase |
50 HP
|
Equipment heat dissipation, current-dependent Pvid |
0 W
|
Heat dissipation capacity Pdiss |
0 W
|
Heat dissipation per pole, current-dependent Pvid |
4.5 W
|
Number of auxiliary contacts (change-over contacts) |
0
|
Number of auxiliary contacts (normally closed contacts) |
0
|
Rated conditional short-circuit current (Iq) |
4 kA (Load side)
100 kA (Supply side) |
Overvoltage category |
III
|
Control circuit reliability |
1 failure per 100,000 switching operations statistically determined, at 24 V DC, 10 mA)
|
Degree of protection (front side) |
IP65
|
Number of poles |
3
|
Mounting method |
Flush mounting
|
Degree of protection |
NEMA 12
|
Suitable for |
Branch circuits, suitable as motor disconnect, (UL/CSA)
Front mounting 4-hole |
Locking facility |
Lockable in the 0 (Off) position
|
Functions |
Emergency switching off function
Interlockable |
Number of switches |
1
|
Safe isolation |
440 V AC, Between the contacts, According to EN 61140
|
Screw size |
M5, Terminal screw
|
Shock resistance |
15 g, Mechanical, According to IEC/EN 60068-2-27, Half-sinusoidal shock 20 ms
|
Lifespan, mechanical |
100,000 Operations
|
Load rating |
2 x Iₑ (with intermittent operation class 12, 25 % duty factor)
1.3 x Iₑ (with intermittent operation class 12, 60 % duty factor) 1.6 x Iₑ (with intermittent operation class 12, 40 % duty factor) |
Switching capacity (auxiliary contacts, general use) |
10A, IU, (UL/CSA)
|
Switching capacity (auxiliary contacts, pilot duty) |
A600 (UL/CSA)
P600 (UL/CSA) |
Terminal capacity |
1 x (2.5 – 35) mm², solid or stranded
2 x (2.5 – 10) mm², solid or stranded 14 – 2 AWG, solid or flexible with ferrule 1 x (1.5 – 25) mm², flexible with ferrules to DIN 46228 2 x (1.5 – 6) mm², flexible with ferrules to DIN 46228 |
Switching capacity (main contacts, general use) |
60 A, Rated uninterrupted current max. (UL/CSA)
|
Safety parameter (EN ISO 13849-1) |
B10d values as per EN ISO 13849-1, table C.1
|
Number of auxiliary contacts (normally open contacts) |
0
|
Number of contacts in series at DC-23A, 120 V |
3
|
Number of contacts in series at DC-23A, 24 V |
1
|
Number of contacts in series at DC-23A, 48 V |
2
|
Number of contacts in series at DC-23A, 60 V |
2
|
Rated breaking capacity at 220/230 V (cos phi to IEC 60947-3) |
640 A
|
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3) |
600 A
|
Rated breaking capacity at 500 V (cos phi to IEC 60947-3) |
590 A
|
Rated breaking capacity at 660/690 V (cos phi to IEC 60947-3) |
340 A
|
Rated making capacity up to 690 V (cos phi to IEC/EN 60947-3) |
800 A
|
Rated operating voltage (Ue) – max |
690 V
|
Rated operating voltage (Ue) – min |
690 V
|
Rated operational voltage (Ue) at AC – max |
690 V
|
Short-circuit current rating (basic rating) |
10 kA, SCCR (UL/CSA)
150A, max. Fuse, SCCR (UL/CSA) |
Short-circuit protection rating |
80 A gG/gL, Fuse, Contacts
|
Rated operational current (Ie) at AC-21, 440 V |
63 A
|
Rated operational current (Ie) at AC-23A, 230 V |
63 A
|
Rated operational current (Ie) at AC-23A, 400 V, 415 V |
63 A
|
Rated operational current (Ie) at AC-23A, 500 V |
63 A
|
Rated operational current (Ie) at AC-23A, 690 V |
63 A
|
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V |
51 A
|
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V |
55 A
|
Rated operational current (Ie) at AC-3, 500 V |
44 A
|
Rated operational current (Ie) at AC-3, 660 V, 690 V |
22.1 A
|
Rated operational current (Ie) at DC-1, load-break switches l/r = 1 ms |
63 A
|
Rated operational current (Ie) at DC-23A, 120 V |
25 A
|
Rated operational current (Ie) at DC-23A, 24 V |
50 A
|
Rated operational current (Ie) at DC-23A, 48 V |
50 A
|
Rated operational current (Ie) at DC-23A, 60 V |
50 A
|
Rated operational current for specified heat dissipation (In) |
63 A
|
Rated operational power at AC-23A, 220/230 V, 50 Hz |
18.5 kW
|
Rated operational power at AC-23A, 400 V, 50 Hz |
30 kW
|
Rated operational power at AC-23A, 500 V, 50 Hz |
45 kW
|
Rated operational power at AC-23A, 690 V, 50 Hz |
55 kW
|
Rated operational power at AC-3, 380/400 V, 50 Hz |
30 kW
|
Rated operational power at AC-3, 415 V, 50 Hz |
30 kW
|
Rated operational power at AC-3, 690 V, 50 Hz |
30 kW
|
Tightening torque |
3 Nm, Screw terminals
26.5 lb-in, Screw terminals |
Uninterrupted current |
Rated uninterrupted current Iu is specified for max. cross-section.
|