R1722 SLP-275 V/4 SALTEK

pluggable module, visual fault signalling, module locking, remote fault signalling

  • four-pole varistor lightning current arrester
  • installation at the boundary of zones LPZ 0 and LPZ 1 or higher, for objects in LPL III and IV
  • for protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages

Technical parameters

Parameter nameParameter value
Type of SPDT1,T2
MountingDIN rail 35 mm
Nominal voltageUn230 V AC
Maximum operating voltageUc275.00 V AC
Maximum operating voltageUc350.00 V DC
Type of networkTN
Maximum overcurrent protection160 A gL/gG
Short-circuit current ratingISCCR50.0 kA
Total discharge current (10/350 µs)ITotal(10/350)50.00 kA
Lightning impulse current (10/350 µs)Iimp12.50 kA
Nominal discharge current (8/20 µs)In30.00 kA
Maximum discharge current (8/20 µs)Imax60.00 kA
Voltage protection levelUp1.50 kV
Voltage protection level at 5 kAUp0.90 kV
Response timeta25 ns
TOV 5 s L-N335 V
TOV characteristic (TOV 5 s)withstand
Cross-section of connected conductors solid (min)1.00 mm2
Cross-section of connected conductors solid (max)35.00 mm2
Cross-section of connected conductors stranded (min)1.00 mm2
Cross-section of connected conductors stranded (max)25.00 mm2
Cross-section of remote indication conductors solid (max)1.5 mm2
Cross-section of remote indication conductors stranded (max)1.5 mm2