HELUKABEL – TRONIC-CY (LiY-CY)

flexible, Cu-screened, colour coded to DIN 47100, EMC-preferred type

EMC = Electromagnetic compatibillity
To optimise the EMC features we recommend a large round contact of the copper braiding on both ends.
CE= The product is conformed with the EC Low-Voltage Directive 2006/95/EG.
Technical data
ㆍSpecial PVC data screened cables,
adapted to DIN VDE, 0812
Temperature range
flexing -5 ㆍC to +80 C
fixed installation -40 *C to +80*C
Nominal voltage
500 V
Test voltage
core/core 1200 V
core/screen 800 V
Breakdown voltage min. 2400 V
Minimum bending radius
flexing 10x cable o
fixed installation 5x cable o
Cable structure
ㆍBare copper, fine wire conductors for
0,5 mm2 to DIN VDE 0295 cl. 5
and IEC 60228 cl.5
ㆍSpecial PVC to DIN EN 50363-3
Cores stranded in layers with optimal
lay-length
ㆍColour coded to DIN 47100, but
without colour repetition
Tinned, copper braided screen,
approx. 65% coverage
ㆍSpecial PVC outer sheath to
DIN EN 50363-4
ㆍColour grey (RAL 7001)
Properties
ㆍExtensively oil resistant,
Chemical Resistance – see table Technical
Informations
ㆍ PVC self-extinguishing and flame retardant
according to IEC 60332-1 (equivalent
DIN VDE 0472 part 804 test method B)
ㆍThe materials used in manufacture are
cadmium-free and contain no silicone and
free from substances harmful to the
wetting properties of lacquers
Note
ㆍHELUKABEL@ -TRONIC-CY is also available in
paired version
(e.g.HELUKABEL@-PAAR-TRONIC-CY
16x2x0, 14 mm2).
ㆍAWG sizes are approximate equivalent
values. The actual cross section is in mm?.
ㆍFor 1 core cable screen of helically wound.
ㆍunscreened analogue type:
TRONIC (LiYY)

flexible, Cu-screened, colour coded to DIN 47100, EMC-preferred type